Product Profile:
- - Underground Service Entrance Cable
- - 600 Volt
- - Aluminum Alloy (AA-8176) Conductor
- - Cross-linked Polyethylene (XLP) Insulation
- - High-Heat and Moisture and Sunlight Resistant
Manufacturer: Joy Sense - World Fourth Largest Aluminum Alloy Cable Manufacturer
Applicaitons:
- - Joysense Type RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the NEC®1
- - May also be used as underground service entrance cable, for direct burial, at conductor temperatures not to exceed 90 Celsuis Degrees
- - When used as RHW-2 or USE-2 conductor temperatures shall not exceed 90 Celsuis Degrees in wet or dry locations.
- - Voltage rating for RHH or RHW-2 or USE-2 conductors is 600V
Standards & References:
Joysense Type RHH or RHW-2 or USE-2 conductors meet or exceed UL Standard 44 (for RHH or RHW-2), UL Standard 854 (for USE-2), Federal Specfication A-A-59544, and requirements of the NEC®.
Construction:
Joysense Type RHH or RHW-2 or USE-2 aluminum conductors are AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene (XLP)
Specifications:
Conductors shall be UL-listed Type RHH or RHW-2 or USE-2, suitable for operation at 600V or less in wet or dry locations, including direct burial in the earth. Conductors shall be Aluminum Alloy, XLP insulated, as manufactured by Joysense Company.
WEIGHTS,MEASUREMENTS AND PACKAGING |
|||||||
CONDUCTOR SIZE (AWG or kcmil) |
INSULATION THICKNESS (mils) |
NOMINAL O.D.(mils) |
AMPACITIES*(AMPS) |
APPROXIMATE NET WEIGHT PER 1000ft(lbs) |
STANDARD PACKAGE |
||
60℃ |
75℃ |
90℃ |
|||||
8 |
60 |
257 |
30 |
40 |
45 |
36 |
B |
6 |
60 |
292 |
40 |
50 |
60 |
49 |
B |
4 |
60 |
336 |
55 |
65 |
75 |
65 |
B |
2 |
60 |
391 |
75 |
90 |
100 |
94 |
B |
1 |
80 |
462 |
85 |
100 |
115 |
126 |
B |
1/0 |
80 |
499 |
100 |
120 |
135 |
151 |
B |
2/0 |
80 |
539 |
115 |
135 |
150 |
182 |
B |
3/0 |
80 |
586 |
130 |
155 |
175 |
221 |
B |
4/0 |
80 |
638 |
150 |
180 |
205 |
269 |
B |
250 |
95 |
713 |
170 |
205 |
230 |
326 |
B |
300 |
95 |
763 |
190 |
230 |
255 |
381 |
B |
350 |
95 |
809 |
210 |
250 |
280 |
435 |
B |
400 |
95 |
852 |
225 |
270 |
305 |
488 |
B |
500 |
95 |
929 |
260 |
310 |
350 |
595 |
B |
700 |
110 |
1100 |
310 |
375 |
420 |
829 |
C |
750 |
110 |
1131 |
320 |
385 |
435 |
881 |
C |
1000 |
110 |
1283 |
375 |
445 |
500 |
1145 |
C |
Allowable Ampacites: 60℃-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. 75℃-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, single-phase services and feeders. All conductors are compact stranded construction comdlying with UL standard 44. |