Product Profile:
- - Type SER and Type SEU
- - 600 Volt Service Entrance Cable
- - Aluminum Alloy (AA-8176) Conductor
- - Individual Conductors Rated XHHW-2 or Aluminum Alloy
- - Sunlight Resistant Jacket and Individual Conductors
Manufacturer: Joy Sense - World Fourth Largest Aluminum Alloy Cable Manufacturer
Applicaitons:
- - Joysense Type SE, service entrance cable is used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, it may be used in all applications wehre Type SE cable is permitted
- - SE cable may be used in wet or dry locations at temperatures not to exceed 90 Celsuis Degrees
- - Voltage rating is 600V
Standards & References:
Joysense Type SE cable meets or exceeds UL Standard 44 for Type XHHW-2 conductors UL Standard 854, Federal Specficaitons A-A 59544, and requirements of the NEC®.
Construction:
Joysense Type SE cable is constructed with sunlight resistant Type XHHW-2 conductor or Type THWN conductors. Aluminum conductors are AA-8000 series Aluminum Alloy, compact stranded. Joysense Type SE, Style R cable assembly plus reinforcement tape are jacketed with gray sunlight resistant polyvinyl chloride (PVC). Available as 2 conductor (2 insulated phase conductors, bare ground), 3 conductor (2 insulated phase conductors, insulated neutral, bare equipment ground), or 4 conductor (3 insultaed phase conducted, insulated neutral, bare equipment ground). Type SE, Style U Cable assemby plus an overall concentrically applied neutral and reinforcement tap are jacketed with gray sunlight resistant polyvinyl choloride (PVC).
Specifications:
- - SER Sample Specification: Cable shall be UL-listed Type SE, Style R, suitable for operation at 600V or less as specified in the NEC®. Conductors shall be Aluminum Alloy, weather resistant PVC jacketed, as manufactured by Joysense Company.
- - SEU Sample Specfications: Cable shall be UL-listed Type SE, Style U, suitable for operation at 600V or less as specified in the NEC®. Conductors shall be Aluminum Alloy, weather resistant PVC jacketed, as manufactured by Joysense Company.
WEIGHTS,MEASUREMENTS AND PACKAGING |
||||||
CONDUCTOR SIZE/CONSTRUCTION (AWG or kcmil) |
NOMINAL O.D.(mils) |
ALLOWABLE AMPACITIES” |
APPROXIMATE NET WEIGHT PER 1000ft(lbs) |
|||
60℃ |
75℃ |
90℃ |
DWELLING |
|||
SER ALUMINUM TOW CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “EZ-SE” ) |
||||||
6-6-6 |
650 |
40 |
50 |
60 |
- |
150 |
4-4-4 |
745 |
55 |
65 |
75 |
- |
203 |
4-4-6 |
745 |
55 |
65 |
75 |
- |
203 |
2-2-2 |
864 |
75 |
90 |
100 |
100 |
290 |
2-2-4 |
864 |
75 |
90 |
100 |
100 |
290 |
2/0-2/0-1 |
1140 |
115 |
135 |
150 |
150 |
527 |
2/0-2/0-2/0 |
1140 |
115 |
135 |
150 |
150 |
527 |
4/0-4/0-2/0 |
1354 |
150 |
180 |
205 |
200 |
784 |
4/0-4/0-4/0 |
1354 |
150 |
180 |
205 |
200 |
784 |
SER THREE CONDUCTOR WITH BARE GROUND (GORMERLY REFERRED TO AS “FOUR CONDUCTOR” ) |
||||||
8-8-8-8 |
612 |
30 |
40 |
45 |
- |
136 |
6-6-6-6 |
717 |
40 |
50 |
60 |
- |
196 |
4-4-4-6 |
823 |
55 |
65 |
75 |
- |
252 |
2-2-2-4 |
956 |
75 |
90 |
100 |
100 |
359 |
1-1-1-3 |
1079 |
85 |
100 |
115 |
110 |
449 |
1/0-1/0-1/0-2 |
1168 |
100 |
120 |
135 |
125 |
540 |
2/0-2/0-2/0-1 |
1264 |
115 |
135 |
150 |
150 |
653 |
3/0-3/0-3/0-1/0 |
1378 |
130 |
155 |
175 |
175 |
793 |
4/0-4/0-4/0-2/0 |
1503 |
150 |
180 |
205 |
200 |
968 |
250-250-250-3/0 |
1576 |
170 |
205 |
230 |
225 |
- |
SER FOUR CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “FIVE CONDUCTOR” 452) |
||||||
2-2-2-2-4 |
1059 |
75 |
90 |
100 |
100 |
452 |
2/0-2/0-2/0-2/0-1 |
1404 |
115 |
135 |
150 |
150 |
827 |
4/0-4/0-4/0-4/0-2/0 |
1672 |
150 |
180 |
205 |
200 |
1228 |
250-250-250-250-3/0 |
1847 |
170 |
205 |
230 |
225 |
- |
SEU TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND (FORMERLY REFERRED TO AS “THREE CONDUCTOR” ) |
||||||
6-6-6 |
430×687 |
40 |
50 |
60 |
- |
145 |
4-4-4 |
499×800 |
55 |
65 |
75 |
- |
198 |
4-4-6 |
474×775 |
55 |
65 |
75 |
- |
181 |
2-2-2 |
569×925 |
75 |
90 |
100 |
100 |
283 |
2-2-4 |
554×910 |
75 |
90 |
100 |
100 |
259 |
2/0-2/0-2/0 |
736×1221 |
115 |
135 |
150 |
150 |
514 |
2/0-2/0-1 |
720×1205 |
115 |
135 |
150 |
150 |
468 |
4/0-4/0-4/0 |
878×1462 |
150 |
180 |
205 |
200 |
765 |
4/0-4/0-2/0 |
835×1419 |
150 |
180 |
205 |
200 |
691 |
Allowable Ampacites: 60℃-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. 75℃-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG. Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, single-phase services and feeders. All conductors are compact stranded construction comdlying with UL standard 44. |