产品中心
北京市朝阳区霞光里15号霄云中心B座1905室
电话: 010-84519511 、84519122
传真: 010-84514688
邮箱: info@luminovogroup.com
SER or SEU : Aluminum Alloy Cable Series
日期: 2014-09-23 15:05:39    点击量:

 

Product Profile: 

  • - Type SER and Type SEU
  • - 600 Volt Service Entrance Cable
  • - Aluminum Alloy (AA-8176) Conductor
  • - Individual Conductors Rated XHHW-2 or Aluminum Alloy
  • - Sunlight Resistant Jacket and Individual Conductors

 

Manufacturer: Joy Sense - World Fourth Largest Aluminum Alloy Cable Manufacturer

 

Applicaitons:

  • - Joysense Type SE, service entrance cable is used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, it may be used in all applications wehre Type SE cable is permitted
  • - SE cable may be used in wet or dry locations at temperatures not to exceed 90 Celsuis Degrees
  • - Voltage rating is 600V

 

Standards & References:

Joysense Type SE cable meets or exceeds UL Standard 44 for Type XHHW-2 conductors UL Standard 854, Federal Specficaitons A-A 59544, and requirements of the NEC®.

 

Construction:

Joysense Type SE cable is constructed with sunlight resistant Type XHHW-2 conductor or Type THWN conductors. Aluminum conductors are AA-8000 series Aluminum Alloy, compact stranded. Joysense Type SE, Style R cable assembly plus reinforcement tape are jacketed with gray sunlight resistant polyvinyl chloride (PVC). Available as 2 conductor (2 insulated phase conductors, bare ground), 3 conductor (2 insulated phase conductors, insulated neutral, bare equipment ground), or 4 conductor (3 insultaed phase conducted, insulated neutral, bare equipment ground). Type SE, Style U Cable assemby plus an overall concentrically applied neutral and reinforcement tap are jacketed with gray sunlight resistant polyvinyl choloride (PVC).

 

Specifications:

  • - SER Sample Specification: Cable shall be UL-listed Type SE, Style R, suitable for operation at 600V or less as specified in the NEC®. Conductors shall be Aluminum Alloy, weather resistant PVC jacketed, as manufactured by Joysense Company.
  • - SEU Sample Specfications: Cable shall be UL-listed Type SE, Style U, suitable for operation at 600V or less as specified in the NEC®. Conductors shall be Aluminum Alloy, weather resistant PVC jacketed, as manufactured by Joysense Company.

 

 

WEIGHTS,MEASUREMENTS AND PACKAGING

CONDUCTOR SIZE/CONSTRUCTION

(AWG or kcmil)

NOMINAL

O.D.(mils)

ALLOWABLE AMPACITIES”

APPROXIMATE

 NET WEIGHT 

PER 1000ft(lbs)

60

75

90

DWELLING

SER ALUMINUM TOW CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “EZ-SE” )

6-6-6

650

40

50

60

-

150

4-4-4

745

55

65

75

-

203

4-4-6

745

55

65

75

-

203

2-2-2

864

75

90

100

100

290

2-2-4

864

75

90

100

100

290

2/0-2/0-1

1140

115

135

150

150

527

2/0-2/0-2/0

1140

115

135

150

150

527

4/0-4/0-2/0

1354

150

180

205

200

784

4/0-4/0-4/0

1354

150

180

205

200

784

SER THREE CONDUCTOR WITH BARE GROUND (GORMERLY REFERRED TO AS “FOUR CONDUCTOR” )

8-8-8-8

612

30

40

45

-

136

6-6-6-6

717

40

50

60

-

196

4-4-4-6

823

55

65

75

-

252

2-2-2-4

956

75

90

100

100

359

1-1-1-3

1079

85

100

115

110

449

1/0-1/0-1/0-2

1168

100

120

135

125

540

2/0-2/0-2/0-1

1264

115

135

150

150

653

3/0-3/0-3/0-1/0

1378

130

155

175

175

793

4/0-4/0-4/0-2/0

1503

150

180

205

200

968

250-250-250-3/0

1576

170

205

230

225

-

SER FOUR CONDUCTOR WITH BARE GROUND (FORMERLY REFERRED TO AS “FIVE CONDUCTOR” 452)

2-2-2-2-4

1059

75

90

100

100

452

2/0-2/0-2/0-2/0-1

1404

115

135

150

150

827

4/0-4/0-4/0-4/0-2/0

1672

150

180

205

200

1228

250-250-250-250-3/0

1847

170

205

230

225

-

SEU TWO CONDUCTOR WITH A BARE CONCENTRIC GROUND 

(FORMERLY REFERRED TO AS “THREE CONDUCTOR” )

6-6-6

430×687

40

50

60

-

145

4-4-4

499×800

55

65

75

-

198

4-4-6

474×775

55

65

75

-

181

2-2-2

569×925

75

90

100

100

283

2-2-4

554×910

75

90

100

100

259

2/0-2/0-2/0

736×1221

115

135

150

150

514

2/0-2/0-1

720×1205

115

135

150

150

468

4/0-4/0-4/0

878×1462

150

180

205

200

765

4/0-4/0-2/0

835×1419

150

180

205

200

691

Allowable Ampacites:
Allowable ampacities shown are for general use as specified by the NEC® ,2008 Edition, section 310.15.

60-When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors.

75-When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.

Dweling –For units. Condutors shall be permitted at listed ampacitees as 120/240 volt, 3-wire, 

single-phase services and feeders.

All conductors are compact stranded construction comdlying with UL standard 44.